01 4503452

Galaxy VL UPS 300 Scalable to 500kW 400/480V Start-up 5x8

Part Number:
GVL300K500DS

Introduction

Highly efficient, modular, high-density 300kW (400/480V) 3-phase UPS that is scalable up to 500kW. It delivers top performance for medium, large, and edge data centers, as well as critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service.

Features

UPS topology

Double-conversion (Online)

Output power

300000 W

Input operation voltage (min)

380 V

Input operation voltage (max)

480 V

Input frequency

40/70 Hz

Output operation voltage (min)

380 V

Output operation voltage (max)

415 V

Number of input phases

3

Number of output phases

3

Crest factor

2.5:1

ECO mode

Yes

Input current Total Harmonic Distortion (THD)

5%

Audible alarm(s)

Yes

Battery

Battery voltage

384 V

Design

Form factor

Tower

Product colour

White

International Protection (IP) code

IP20

Certification

FCC B, IEC 60721-4-2, 2M2, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, UL 1778, 5ª, VFI-SS-111

Operational conditions

Operating temperature (T-T)

0 - 40 °C

Storage temperature (T-T)

-25 - 55 °C

Operating relative humidity (H-H)

0 - 95%

Storage relative humidity (H-H)

10 - 80%

Operating altitude

0 - 3000 m

Technical details

Sustainability compliance

Yes

Sustainability certificates

RoHS

Weight & dimensions

Width

850 mm

Depth

925 mm

Height

1970 mm

Weight

570 kg

Package width

950 mm

Package depth

1100 mm

Package height

2145 mm

Package weight

744 kg

No options for this product
.