Features
UPS topology
Double-conversion (Online)
Output power capacity
10 kVA
Output power
10000 W
Waveform
Pure sine
Input operation voltage (min)
304 V
Input operation voltage (max)
477 V
Input frequency
45/65 Hz
Output operation voltage (min)
380 V
Output operation voltage (max)
415 V
Output frequency regulation
50/60 Hz
Maximum current
18 A
Number of input phases
3
Number of output phases
3
Input power factor
0.99
Output voltage Total Harmonic Distortion (THD)
3%
Input current Total Harmonic Distortion (THD)
3%
Noise level
60 dB
Battery
Battery technology
Sealed Lead Acid (VRLA)
Battery voltage
220 V
Number of batteries supported
3
Typical backup time at full load
15 min
Design
Form factor
Tower
Product colour
White
International Protection (IP) code
IP20
Certification
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Operational conditions
Operating temperature (T-T)
0 - 40 °C
Storage temperature (T-T)
-15 - 40 °C
Operating relative humidity (H-H)
0 - 95%
Storage relative humidity (H-H)
0 - 95%
Operating altitude
0 - 999.9 m
Non-operating altitude
0 - 15000 m
Weight & dimensions
Width
380 mm
Depth
928 mm
Height
1400 mm
Weight
112 kg
Package width
563 mm
Package depth
1014 mm
Package height
1640 mm
Package weight
145 kg
Packaging data
Quick installation guide
Y
Other features
Output voltage
400 V